Four functions for computing boiling temperature are tested and the results are compared to data from the CRC Handbook of Physics and Chemistry.
METHODS AND RESULTS.
Method 1: Constant lυ.
In the first method, the boiling temperature of water was computed for the pressures between mean sea level pressure (MSLP; 1,013.25 hPa) and the lower pressure (high elevation) limit shown on most skew T–logp diagrams (100 hPa) using (3) and the value of lυ at 50°C (2.3893 × 106 J kg−1) from Table 1 (Tsonis 2007). This value of lυ was chosen for two reasons: 1) its corresponding temperature is midway between the known boiling temperatures at MSLP and at pressures near the top of the stratosphere and 2) doing so made it possible to determine the accuracy of the results when only a rough approximation of the parameter is used. The results are shown in Table 2.
Latent heat of vaporization for water. Some values have been interpolated from available data (Tsonis 2007).
Comparison of boiling temperature values computed from the Clausius–Clapeyron equation with constant lυ (method 1) to values from Lide (2006). Elevations correspond to the U.S. Standard Atmosphere (NASA 1962, 1966, 1976).
These results indicate that, to within less than half a percentage point (mean error 0.33%) and about 1.15°C (mean bias), the Clausius–Clapeyron equation can be used to estimate the boiling point temperature of water in pressures typical of Earth’s lower atmosphere, even when using a rough estimate of the value of the latent heat of vaporization.
Method 2: Linearly varying lυ.
In the error-reduction loop for method 2, a first-guess temperature was used to estimate the value of lυ with (5), and the inverted Clausius–Clapeyron equation (3) was then used with the estimated lυ to compute the boiling temperature at a selected pressure. The resulting temperature was then substituted into the latent heat relationship (5), yielding an updated value of lυ, and the process was repeated. This was continued for each selected pressure level until the resulting boiling temperature from (3) and the guess temperature used for lυ in (5) were within 0.01°C. This method was used to compute boiling temperatures for the same pressures listed in Table 2, then compared to boiling point temperatures from Lide (2006). The results are shown in Table 3 and indicate a mean bias of about 6.45°C and a mean error of about 1.78% in the applicable range of pressures. Both of these are larger than the results described in Table 2. That is, by substituting this functional value of lυ for the fixed value (in an attempt to improve the prediction of boiling point temperature), the results got worse, not better.
Comparison of boiling temperature values computed with linear-function lυ (method 2) to values from Lide (2006). Bias and error are as defined in text.
Method 3: Second-order polynomial function for lυ.

The values of lυ as a function of temperature between 0° and 100°C (in 1°C increments) were estimated by
computing saturation vapor pressure with (1), which uses the temperature-dependent variable value of lυ, starting with a first-guess value of lυ;
computing saturation vapor pressure with (6), which uses the fixed value of lυ0; and
adjusting the variable value of lυ used in (1) to systematically minimize the difference between the two vapor pressures.
Latent heat of vaporization as a function of temperature, computed by method 3.
Citation: Bulletin of the American Meteorological Society 98, 7; 10.1175/BAMS-D-16-0174.1
From here, a second error-reduction loop was used to compute the boiling temperature as a function of pressure. In this loop, a first-guess temperature was used to compute the latent heat term using (7), and (3) was then used to compute the boiling temperature at a selected pressure. The resulting temperature was then substituted into the latent heat relationship (7), and the process was repeated. This was continued until the resulting boiling temperature from (3) and the guess temperature used for lυ in (7) were within 0.01°C. This method was used to compute boiling temperatures for pressures between 50 and 1,080 hPa, in 1-hPa increments. The results were stored in a file with two columns (one containing pressure and the other boiling temperature) and are plotted in Fig. 2.
Boiling temperature as a function of pressure, computed by method 3.
Citation: Bulletin of the American Meteorological Society 98, 7; 10.1175/BAMS-D-16-0174.1
Sample values of the boiling temperature computed with (7) in the error-reduction loop were compared to boiling point temperatures taken from Lide (2006), which is summarized in Table 5. The bias and error values shown in columns 4 and 5 of Table 5 indicate the results are still warm relative to the Lide (2006) values, but to a smaller degree than the results of the calculations that used the fixed value of lυ (Table 2), and to a much lesser degree than the calculations using the linear-functional lυ (Table 3). The mean bias is 0.31°C, and the mean error in the range of pressures shown is 0.08%.
Comparison of boiling temperature values computed with second-order function lυ (method 3) to values from Lide (2006).
Method 4: Polynomial fits to method 3 results.
Coefficients for fifth-order polynomial fit for boiling temperature as a function of pressure (method 4).
Sample values of the boiling temperature computed with (8) were compared to boiling point temperatures taken from Lide (2006) and are summarized in Table 7. The bias and error values shown in columns 4 and 5 of Table 7 indicate this function is also slightly warm relative to the Lide (2006) values. The mean bias is 0.25°C, and the mean error in the range of pressures shown is 0.09%.
Comparison of boiling temperature values computed with fifth-order polynomial (method 4) to values from Lide (2006).
SUMMARY AND CONCLUSIONS.
Boiling is an extreme form of evaporation that occurs when the saturation vapor pressure is equal to the total atmospheric pressure (Glickman 2000). The Clausius–Clapeyron equation (1) was recast to describe the boiling point (2) and solved for boiling temperature (3). Since one term in the equation is the latent heat of vaporization lυ, which is a function of temperature, one can either use an approximation of lυ to compute boiling temperature TB at a given pressure PB or use a temperature-dependent functional expression of lυ and proceed through an error-reduction loop. The purposes and motivation of this research were 1) to test one constant value and two temperature-dependent functional expressions for lυ in the Clausius–Clapeyron equation and 2) to derive a simple polynomial function, with atmospheric pressure as the independent variable, to compute boiling temperature. Values of boiling temperature as a function of pressure as reported in Lide (2006) were used as the standard by which all four methods were judged. Results are summarized in Table 8.
Comparison of mean bias and error between MSLP and 100 hPa for methods tested to compute boiling temperature.
The first method used the value of lυ valid for 50°C and obtained results that were correct to within a mean error of 0.33% and a mean bias of 1.15°C for pressures typical of Earth’s troposphere and lower stratosphere. The second method used the linear expression for lυ described by (5) (Rogers and Yau 1989), and the result was an even greater disagreement between computed values of TB from (3) and those listed in Lide (2006), with a mean bias of about 6.45°C between MSLP and 100 hPa (indicating computed values of the boiling temperature were too warm) and a mean error of about 1.78%.
The third method began by deriving a new, second-order, temperature-dependent polynomial (7) for lυ. The new function for lυ yields a mean latent heat error of 1.28% between 0° and 50°C when compared to those listed in Tsonis (2007), and a probable error at 100°C of about 5%. An error-reduction loop was used to compute the boiling temperature as a function of pressure, wherein a first-guess temperature was used to compute the latent heat coefficient using the second-order polynomial shown in (7), and (3) was then used to compute the boiling temperature at a selected pressure. The resulting temperature from (3) was then substituted into the latent heat relationship (7), and the process was repeated until the resulting boiling temperature from (3) and the guess temperature used for lυ in (7) were within 0.01°C. This method was used to compute boiling temperatures for pressures between 50 and 1,080 hPa, in 1-hPa increments. This method for computing TB showed a warm bias (mean value 0.31°C between MSLP and 100 hPa) compared to Lide (2006) and a mean error about 4 times smaller than those associated with computed values of TB that used the constant value of lυ.
The fourth method fitted a fifth-order polynomial (eliminating lυ and making PB the sole independent variable) to the boiling temperatures resulting from the third method (8). The polynomial shows an R2 value of 0.9998 and fit standard deviation of 0.2377°C. Computed values of TB using the polynomial were associated with a mean bias of 0.25°C and a mean error of 0.09% when compared to Lide (2006).
ACKNOWLEDGMENTS
I wish to thank my colleagues R. Bruce Telfeyan, Don S. Harper III, and Stephen Augustyn, as well as three anonymous reviewers, for their valuable feedback. I would also like to thank my colleague Jason Cordeira for his assistance.
REFERENCES
Brock, F. V., and S. J. Richardson, 2001: Meteorological Measurement Systems. Oxford University Press, 290 pp.
Court, A., 1985: Comment on paper ‘A new formula for latent heat of vaporization of water as a function of temperature’, by B. Henderson-Sellers (1984, 110, 1186–1190). Quart. J. Roy. Meteor. Soc., 112, 283–284, doi:10.1002/qj.49711247117.
Glickman, T. S., Ed., 2000: Glossary of Meteorology. 2nd ed. Amer. Meteor. Soc., 855 pp. [Available online at http://glossary.ametsoc.org/.]
Henderson-Sellers, B., 1984: A new formula for latent heat of vaporization of water as a function of temperature. Quart. J. Roy. Meteor. Soc., 110, 1186–1190, doi:10.1002/qj.49711046626.
Henderson-Sellers, B., 1985: Reply to “Comment on paper ‘A new formula for latent heat of vaporization of water as a function of temperature,’ by B. Henderson-Sellers (1984, 110, 1186–1190)” by A. Court. Quart. J. Roy. Meteor. Soc., 112, 284.
Lide, D. R., Ed., 2006: CRC Handbook of Chemistry and Physics. 87th ed. CRC Press, 2608 pp.
Miller, S., 2015: Applied Thermodynamics for Meteorologists. Cambridge University Press, 385 pp.
NASA, 1962: U.S. Standard Atmosphere, 1962. U.S. Government Printing Office, 290 pp. [Available online at www.dtic.mil/cgi-bin/GetTRDoc?Location=U2&doc=GetTRDoc.pdf&AD=AD0659893.]
NASA, 1966: U.S. Standard Atmosphere Supplements, 1966. U.S. Government Printing Office, 300 pp. [Available online at www.dtic.mil/cgi-bin/GetTRDoc?Location=U2&doc=GetTRDoc.pdf&AD=AD0659543.]
NASA, 1976: U.S. Standard Atmosphere, 1976. U.S. Government Printing Office, 241 pp. [Available online at http://ntrs.nasa.gov/archive/nasa/casi.ntrs.nasa.gov/19770009539_1977009539.pdf.]
Rogers, R. R., and M. K. Yau, 1989: A Short Course in Cloud Physics. 3rd ed. Butterworth-Heinemann, 290 pp.
Tsonis, A. A., 2007: An Introduction to Atmospheric Thermodynamics. 2nd ed. Cambridge University Press, 187 pp.